System | |
Процессор | 16-bit CPU |
SRAM | 768 KB |
Flash Memory | 512 KB |
EEPROM | 16 KB |
Сторожевой таймер | Да (0.8 секунд) |
NVRAM | 31 Bytes |
Часы реального времени | RTC Provide seconds, minutes, hours, date of week/month month and year |
microSD | Yes, can support 1 or 2 GB microSD |
Интерфейсы | |
PoE Ethernet Port | RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators) |
COM 1 | RS-232 (Reserved, Unsupported by WISE firmware) |
COM 2 | RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed : 115200 bps max. |
LED Indicators | |
System LED | Yes (Red) |
Светодиодный LED-экран | - |
Ethernet Link LED | Yes (Green : Ethernet link detected, Flashing Green : Ethernet packet received) |
Hardware Expansion | |
I/O Expansion Bus | Да |
Power Requirements | |
Reserve Polarity Protection | Да |
Consumption | 2.0 W |
Frame Ground | Yes (for ESD Protection) |
Input Range | +12 ~ +48 VDC |
Redundant Power Input | Да |
Mechanical | |
Габариты (Ш x В x Г) | 91 mm x 123 mm x 52 mm |
Installation | DIN-Rail |
Environment | |
Рабочая температура | -25 °C ~ +75 °C |
Допустимая температура в режиме хранения | -30 °C ~ +80 °C |
Влажность | 10 ~ 90% RH, non-condensing |
Functions | |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers | Delay / Timing functions |
12 Schedules | Setup prescheduled routine tasks. |
12 Emails | Send Email messages to pre-set Email receivers. |
12 CGI Commands | Send pre-set CGI commands. |
12 Recipes | Set up THEN/ELSE action groups. |
Modbus/TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
Data Logger | Set up the Data Logger configuration, include the data record format, and data file sending operation. |
IF Conditions | |
DI Channel | ON, OFF, ON to OFF, OFF to ON, Change |
AI Channel | =, and lt , and gt , and gt =, and lt = (value) |
Internal Register | =, and lt , and gt , and gt =, and lt = (value) |
DI Counter | =, and gt , and lt , and gt =, and lt =(value), Change |
Timer | Timeout, Not Timeout |
Schedule | In Range, Out of Range |
Rule Status | Enable, Disable |
THEN / ELSE Actions | |
DO Channel | ON, OFF, Pulse Output |
AO Channel | Change the value |
Internal Register | Change the value |
DI Counter | Reset |
Timer | Start, Stop |
Schedule | Start, Stop |
Send | |
CGI Commands | Send |
Recipe | Execute |
Rule Status | Enable, Disable |
Data Logger | Start, Stop, One-Time Log |