Ничего не куплено!
Продажа и внедрение оборудования для промышленной автоматизации
Mail: prom@protonpc.ru
Тел: (495) 789-41-64 доб. 303
Supply | ||
Rated voltage | 7.2 V DC , battery operated | |
Электрические параметры | ||
Output rated operating current | 4 ... 20 mA | |
Питание | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Вход | ||
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - до four externally powered HART field devices operating in multidrop mode | |
Подключение | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Протокол | HART 7.1, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - до 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Выход | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: до four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of Диапазон измерений | |
Influence of ambient temperature | current input: 5 µ-A/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of до ten burst messages in a wireless network, period and trigger mode selectable - notification of до five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Соответствие директивам | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Стандарты защищенности | IEC 60529 | |
Условия окружающей среды | ||
Рабочая температура окружающей среды | -40 ... 80 °C (-40 ... 176 °F) | |
Температура хранения устройства | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Физические/механические параметры | ||
Стандарты защищенности | IP66 | |
Материал корпуса | plastic | |
Масса | приблизительно 750 g | |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 in) (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting versions see type code |