Fieldbus interface | ||
Main cable (Trunk) | ||
Connection | input (Trunk IN): terminals 1+, 2-, 3s output (Trunk OUT): terminals 4+, 5-, 6s | |
Rated voltage | max. 35 V DC | |
Rated current | 3 A DC | |
Outputs | ||
Connection | Spur 1: terminals 10+, 11-, 12s Spur 2: terminals 13+, 14-, 15s Spur 3: terminals 16+, 17-, 18s Spur 4: terminals 19+, 20-, 21s Spur 5: terminals 22+, 23-, 24s Spur 6: terminals 25+, 26-, 27s Spur 7: terminals 28+, 29-, 30s Spur 8: terminals 31+, 32-, 33s | |
Rated voltage | see main cable | |
Rated current | see main cable | |
Соответствие директивам | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Соответствие стандартам | ||
Electromagnetic compatibility | NAMUR NE 21, EN 61326 | |
Стандарты защищенности | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | DIN IEC 721 | |
Условия окружающей среды | ||
Рабочая температура окружающей среды | see table | |
Температура хранения устройства | -40 ... 85 °C (-40 ... 185 °F) | |
Физические/механические параметры | ||
Тип подключения | ||
Main cable (Trunk) | Terminals | |
Поперечное сечение | до 2.5 mm2 | |
Cable diameter | ||
Main cable (Trunk) | 5 ... 10 mm | |
Корпус | 258 mm x 114 mm x 84 mm (without cable glands) | |
Стандарты защищенности | IP67 | |
Масса | 1800 g | |
Mounting | panel mounting | |
Data for application in connection with Ex-areas | ||
Main cable (Trunk) | only for connection to intrinsically safe fieldbus circuits | |
Maximum values | ||
Voltage | max. 35 V | |
Current | max. 3 A | |
Соответствие директивам | standards | |
Directive 94/9/EC | EN 50014, EN 50020, EN 50284 |