Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus | |
Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) | |
ITK version | 4.51 | |
Implementation | resource block function block transducer block | |
Execution time | AI, MAI 40 ms max. | |
Macro cycle | typical for one device 8xAI or 1xMAI max. 500 ms | |
Firmware update | via separate штекерный разъем | |
FDE (Fault Disconnect Equipment) | 6.7 mA | |
Polarity | not polarity sensitive | |
Rated voltage | 9 ... 32 V | |
Rated current | max. 23 mA | |
Индикаторы состояния и их значение | ||
LED PWR | green: on, bus voltage existent | |
LED COM ERR | red: continuous lightning: hardware error- 2 Hz flashing: no bus activities or bus fault- off: no error | |
LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange- off: no error | |
Вход | ||
Number | 8 | |
Sensor types | see table 3 | |
Grounding | grounding of thermoelements possible | |
Error detection | lead breakage, wiring error, hardware device error | |
Common mode voltage | Input to Input 600 Vpeak | |
Transfer characteristics | ||
Deviation | ||
Linearization | T/C input 0.1°C RTD input 0.03°C | |
Internal measurement cycle | for all sensor types max. 1 s | |
Electrical isolation | ||
Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Соответствие директивам | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Соответствие стандартам | ||
Electrical isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2006 | |
Стандарты защищенности | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Условия окружающей среды | ||
Рабочая температура окружающей среды | see table 1 | |
Температура хранения устройства | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le- 95 % non-condensing , for DIN rail version only | |
Shock resistance | ||
R... DIN rail housing | 15 g | |
F2... aluminum housing | 15 g , 11 ms | |
Vibration resistance | ||
R... DIN rail housing | 5 g 10 ... 150 Hz | |
F2... aluminum housing | 10 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Физические/механические параметры | ||
Тип подключения | plug-in terminals | |
Поперечное сечение | ||
Bus | до 2.5 mm2 | |
Inputs | до 2.5 mm2 | |
Cable diameter | see table 2 | |
Cable gland | sensor inputs M16, fieldbus M20 | |
Материал | ||
R... DIN rail housing | Polycarbonate | |
F2... aluminum housing | ALSI12 (Cu) DIN1725 (Si 1.2%), anodized | |
Стандарты защищенности | ||
R... DIN rail housing | IP20 | |
F2... aluminum housing | IP67 | |
Масса | ||
R... DIN rail housing | 360 g | |
F2... aluminum housing | 1800 g | |
Mounting | panel or DIN rail mounting | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | PTB 03 ATEX 2237 | |
Group, category, type of protection, temperature class | II 2(1G/D) G Ex ia IIC T4 , II (1)GD [Ex ia] IIC | |
Bus | FISCO see EC-Type Examination Certificate | |
Inputs | see EC-Type Examination Certificate | |
Statement of conformity | PTB 03 ATEX 2238 X | |
Group, category, type of protection, temperature class | II 3G Ex nA II T4 , II 3G Ex nL IIC T4 , II (3)G [Ex nL] IIC | |
Electrical isolation | ||
Bus | see Statement of Conformity | |
Input | see EC-Type Examination Certificate | |
Соответствие директивам | ||
Directive 94/9/EC | EN 60079-0:2006 , EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-27:2006 |