Ничего не куплено!
Продажа и внедрение оборудования для промышленной автоматизации
Mail: prom@protonpc.ru
Тел: (495) 789-41-64 доб. 303
Fieldbus interface | ||
Main cable (Trunk) | ||
Connection | see table 1 | |
Rated voltage | 9 ... 31 V DC | |
Rated current | max. 6 A | |
Screening option | looped through direct to ground potential, trunk and outputs | |
Outputs | ||
Connection | see table 1 | |
Rated voltage | max. 31 V | |
Rated current | max. 40 mA | |
Short-circuit current | max. 45 mA | |
Screening option | looped through direct to ground potential, trunk and outputs | |
Self current consumption | max. 9 mA | |
Voltage drop main cable/outputs | max. 1.3 V | |
Terminating resistor | switchable 100 &Omega- integrated | |
Surge protection | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V | |
Индикаторы состояния и их значение | ||
LED voltage Fieldbus | green: Fieldbus voltage > 10 V | |
LED status Fieldbus | yellow: bus activity | |
LED status output | red flashing: short-circuit | |
Соответствие директивам | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Соответствие стандартам | ||
Electromagnetic compatibility | NE 21:2006 | |
Стандарты защищенности | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Условия окружающей среды | ||
Рабочая температура окружающей среды | see table 2 | |
Температура хранения устройства | -40 ... 85 °C (-40 ... 185 °F) | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Физические/механические параметры | ||
Тип подключения | see table 2 | |
Поперечное сечение | до 2.5 mm2 | |
Cable diameter | see table 3 | |
Cable gland | see table 2 | |
Корпус | see figure 1 | |
Материал корпуса | ||
R... DIN rail housing | PA 6.6 | |
F2... aluminum housing | ALSI12 (Cu) DIN1725 (Si 1.2%), anodized | |
Стандарты защищенности | ||
R... DIN rail housing | IP20 | |
F2... aluminum housing | IP67 | |
Масса | ||
R... DIN rail housing | 380 g | |
F2... aluminum housing | 1800 g | |
Mounting | panel or DIN rail mounting | |
Data for application in connection with Ex-areas | ||
Main cable (Trunk) | ||
Rated current | max. 2.5 A | |
Outputs | ||
Voltage | 32 V | |
Current | 45 mA | |
Inductance | 0.25 mH | |
Capacitance | 100 nF | |
Statement of conformity | TUV 04 ATEX 2465 X | |
Group, category, type of protection, temperature class | II 3G EEx nA [L] IIC T4 | |
Declaration of conformity | PF 08 CERT 1212 Valid for F2 housing solution without plug connectors | |
Group, category, type of protection, temperature class | II 3 D Ex tD A22 IP54 T135 °C (non-conductive dust) | |
Соответствие директивам | ||
Directive 94/9/EC | EN 50021:1999 , EN 61241-0:2004 , EN 61241-1:2004 | |
International Сертификаты | ||
FM approval | CoC 3026284, CoC 3026284C | |
Control drawing | No. 116-0280 | |
Approved for | Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, Ex nA [nL] IIC T4 | |
CSA approval | CoC 1723350 | |
Control drawing | No. 116-0280 | |
Approved for | Class I, Zone 2, Ex nA [nL] IIC T4 |