Ничего не куплено!
Продажа и внедрение оборудования для промышленной автоматизации
Mail: prom@protonpc.ru
Тел: (495) 789-41-64 доб. 303
Fieldbus interface | ||
Main cable (Trunk) | ||
Connection | input (Trunk IN): terminals 3+, 4-, 5s output (Trunk OUT): terminals 7-, 8+, 6s | |
Rated voltage | 32 ... 16 V DC | |
Rated current | 31 mA ... 26 mA (without load) 77 mA ... 115 mA (at 20 mA load per input) 120 mA ... 209 mA (at 40 mA load per input) 135 mA ... 241 mA (short-circuit on all outputs) | |
Outputs | ||
Connection | output 1: terminals 10+, 11-, 12S shield- output 2: terminals 13+, 14-, 15S shield- output 3: terminals 16+, 17-, 18S shield- output 4: terminals 19+, 20-, 21S shield | |
Rated voltage | 10 ... 13 V | |
Rated current | max. 43 mA | |
Short-circuit current | 50 mA | |
Индикаторы состояния и их значение | ||
LED voltage Fieldbus | green: on, bus voltage existent | |
LED status output | red flashing: short-circuit | |
Electrical isolation | ||
Main wire/outputs | isolation is not affected by interference according to EN 60079-11, voltage peak value 375 V | |
Соответствие директивам | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Соответствие стандартам | ||
Electromagnetic compatibility | NE 21:2006 | |
Стандарты защищенности | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | DIN IEC 721 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Условия окружающей среды | ||
Рабочая температура окружающей среды | see table 2 | |
Температура хранения устройства | -40 ... 85 °C (-40 ... 185 °F) | |
Физические/механические параметры | ||
Тип подключения | see table 2 | |
Поперечное сечение | до 2.5 mm2 | |
Cable diameter | see table 3 | |
Cable gland | see table 2 | |
Корпус | see figures 1 and 2 | |
Материал корпуса | ||
R... DIN rail housing | PA 6.6 | |
F2... aluminum housing | ALSI12 (Cu) DIN1725 (Si 1.2%), anodized | |
Стандарты защищенности | see table 5 | |
Масса | see table 5 | |
Mounting | see table 5 | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | PTB 02 ATEX 2086 | |
Group, category, type of protection, temperature class | II 2 G (1) Ex e mb [ia Ga] IIC T4 Gb II 2 G (1D) Ex e mb [ia Da] IIC T4 Gb | |
Main cable (Trunk) | ||
Maximum safe voltage | 253 V AC | |
Outputs | in accordance to FISCO | |
Voltage | 15.75 V | |
Current | 248 mA | |
Power | 975 mW | |
Declaration of conformity | PF 08 CERT 0579 Valid for F2 housing solution without plug connectors | |
Group, category, type of protection, temperature class | II 3 D Ex tD A22 IP54 T135 °C (non-conductive dust) | |
Соответствие директивам | ||
Directive 94/9/EC | EN 60079-0:2009 , EN 60079-7:2007 , EN 60079-11:2007 , EN 60079-18:2009 | |
International Сертификаты | ||
FM approval | CoC 3015728 | |
Control drawing | No. 116-0226 | |
Approved for | Class I, Division 2, Groups A, B, C, D / Class I, Zone 2, AEx nA [ia] IIC T4 | |
CSA approval | CoC 1592754 | |
Control drawing | 116-0266 | |
Approved for | Class I, Division 2, Groups A, B, C, D / Class I, Zone 2, Ex nA [ia] IIC T4 | |
IECEx approval | IECEx PTB 03.0003 | |
Approved for | Ex me [ia] IIC T4 | |
Certificates and Сертификаты | ||
Marine approval | DNV A-10798 |