Supply | ||
Подключение | backplane bus | |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** | |
Потребляемая мощность | 2 W | |
Auxiliary energy | 24 V DC Trunk load 10 mA according to FF standard. | |
Fieldbus interface | ||
FOUNDATION Fieldbus | ||
Connection | wired to Ex e terminals via backplane | |
Baud rate | 31.25 kBit/s , MBP | |
Протокол | H1 to IEC 1158-2 | |
Station connection | directly at the trunk or via spur protector | |
Number of stations per bus line | 1 or 2, depending on the required response times | |
Number of channels per station | max. 20 analog, max. 40 digital | |
Supported I/O modules | 5 slots, to be filled with (combinations possible): 1*08 digital input, 8-channel, NAMUR 3*05 analog input, 4-channel, 20 mA (HART via service bus) 4*05 Аналоговый выход, 4-channel, 20 mA (HART via service bus) 5204 Pt100 RTD input, 4-channel 5205 thermocouple input, 4-channel 6305 relay output, 4-channel, 230 V 6306 relay output, 8-channel, 24 V 6*08 digital output, 8-channel, Ex i 6210-6215 digital output, 4-channel, Ex i power * = variable (2=IS, 3=Ex e) | |
Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) | |
Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) | |
Addressing | via DCS (Software) | |
Internal bus | ||
Подключение | backplane bus | |
Indicators/settings | ||
LED indicator | зеленый светодиод (power supply): On = operating, fast flash = cold start красный светодиод (collective alarm): On = internal fault, flashing = no fieldbus желтый светодиод (operating mode): Flashing = active | |
Соответствие директивам | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Стандарты защищенности | IEC 60529 | |
Условия окружающей среды | ||
Рабочая температура окружающей среды | -20 ... 60 °C (-4 ... 140 °F) | |
Температура хранения устройства | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100 | |
Vibration resistance | frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ±- 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz | |
Damaging gas | for plugs: 21 days in 25 ppm SO2, at 25 °C and 75 % rel. humidity, device G3 | |
Физические/механические параметры | ||
Стандарты защищенности | IP20 (module) , a separate housing is required acc. to the system description | |
Подключение | via backplane | |
Масса | приблизительно 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 in) | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | PTB 97 ATEX 1074 U , PTB 97 ATEX 1075 (system) , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection | II 2 G Ex d IIC | |
Питание | only in connection with the power supplies FB92** | |
Соответствие директивам | ||
Directive 94/9/EC | EN 60079-0 , EN 60079-1 | |
International Сертификаты | ||
IECEx approval | pending |
Совместимое оборудование | Наименование |
Remote I/O System - LB/FB | DTM collection |