Ничего не куплено!
Продажа и внедрение оборудования для промышленной автоматизации
Mail: prom@protonpc.ru
Тел: (495) 789-41-64 доб. 303
Описание: | Unmanaged switch in accordance with IEEE 802.3, store-and-forward-switching, Fast-Ethernet (10/100 Mbit/s) ports. |
Тип: | OCTOPUS OS20-001000T5T5TAFUHB |
Артикул производителя: | 942 025-001 |
Количество и типы интерфейсов: | 10 x 10/100 BASE-TX, M12 D coding, 4-pole, TP cable auto-crossing, auto-negotiation, auto-polarity |
Operating temperature | -40 °C ... 70 °C |
Доступность для заказа: | выпускается |
Description | Unmanaged switch in accordance with IEEE 802.3, store-and-forward-switching, Fast-Ethernet (10/100 Mbit/s) ports. |
Port type and quantity | 10 x 10/100 BASE-TX, M12 D coding, 4-pole, TP cable auto-crossing, auto-negotiation, auto-polarity |
Type | OCTOPUS OS20-001000T5T5TAFUHB |
Order No. | 942 025-001 |
Power supply/signaling contact | 1 x M12 5-pin connector, A coding, no signaling contact |
V.24 interface | n/a |
USB interface | n/a |
Twisted pair (TP) | 0 m ... 100 m |
Multimode fiber (MM) 50/125 µm | n/a |
Multimode fiber (MM) 62.5/125 µm | n/a |
Single mode fiber (SM) 9/125 µm | n/a |
Line - / star topology | any |
Ring structure (HIPER-Ring) quantity switches | n/a |
Operating voltage DC | 24 V ... 48 V |
Power consumption | 6 W |
Current consumption at 24 V DC | 220 mA |
Current consumption at 48 V DC | 110 mA |
Diagnostics | LEDs (power 1, power 2, link status, data) |
Configuration | n/a |
Security | n/a |
Redundancy functions | n/a |
Operating temperature | -40 °C ... 70 °C |
Storage/transport temperature | -40 °C ... 85 ?C |
Relative humidity (also condensing) | 10 % ... 100 % |
MTBF | 30 years- MIL-HDBK 217F- Gb 25°C |
Dimensions (W x H x D) | 184 mm x 189 mm x 70 mm |
Mounting | Wall mounting |
Weight | 1150 gram |
Класс защищенности | IP54 |
IEC 60068-2-27 (ударопрочность) | 15 g, 11 ms duration, 18 shocks |
IEC 60068-2-6 (виброзащищенность) | 1 mm, 2 Hz-13.2 Hz, 90 min.- 0.7 g, 13.2 Hz-100 Hz, 90 min.- 3.5 mm, 3 Hz-9 Hz, 10 cycles, 1 octave/min.- 1 g, 9 Hz-150 Hz, 10 cycles, 1 octave/min |
EN 61000-4-2 electrostatic discharge (ESD) | 6 kV contact discharge, 8 kV air discharge |
EN 61000-4-3 electromagnetic field | 20 V/m (80-1000 MHz) |
EN 61000-4-4 fast transients (burst) | 2 kV power line, 1 kV data line |
EN 61000-4-5 surge voltage | power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line |
EN 61000-4-6 conducted immunity | 10 V (150 kHz-80 MHz) |
FCC CFR47 Part 15 | FCC 47 CFR Part 15 Class A |
EN 55022 | EN 55022 Class A |
Safety of industrial control equipment | cUL 60950-1 (pending) |
Hazardous locations | n/a |
Shipbuilding | Germanischer Lloyd (pending) |
Employment in vehicles | E1 (pending) |
Electronic mechanisms on rail-mounted vehicles | EN 50155, EN 50121-4, DIN 5510-2, NF F 16-101, NF F 16-102 |
Scope of delivery | covers for sealing unused ports, M12-connector (ELWIKA 5012 PG7) for power connection, description and operating instructions |
Note | Please note that some recommended accessory parts only support a temperature range from -25 ?C to +70 °C and might limit the possible operating conditions for the entire system. |