Function and system design | ||
Measuring principle | The sensor of the LUC-M** transmits ultrasonic pulses in the direction of the product surface. There, they are reflected back and received by the sensor. The LUC-M** measures the time between pulse transmission and reception. The instrument uses the time (and the velocity of sound) to calculate the distance between the sensor membrane and the product surface. As the device knows the empty distance from a user entry, it can calculate the level. | |
Equipment architecture | 4 ... 20 mA output with HART Протокол system integration via PROFIBUS PA | |
Input characteristics | ||
Measured variable | distance between the sensor membrane and the product surface using the linearization function, the device calculate - level in any units - volume in any units - flow across measuring weirs or open channels in any units | |
Measurement range | LUC-M10: max. 5 m (16.4 ft) in fluids and 2 m (6.6 ft) in bulk materials LUC-M20: max. 8 m (26.2 ft) in fluids and 3,5 m (11.5 ft) in bulk materials LUC-M30: max. 15 m (49.2 ft) in fluids and 7 m (23 ft) in bulk materials LUC-M40: max. 10 m (32.8 ft) in fluids and 5 m (16.4 ft) in bulk materials | |
Output characteristics | ||
Output signal | according to the instrument version: - 4 ... 20 mA with HART Протокол - PROFIBUS PA | |
Auxiliary energy | ||
Electrical connection | terminal compartment: In the F12 housing, the terminals are located underneath the housing cover, in the T12 housing, they are under the cover of the separate terminal compartment. cable gland: M20 x 1.5 (recommended cable diameter 6 ... 10 mm (0.24 ... 0.4 in)) cable entry G1/2 or 1/2 NPT PROFIBUS PA: M12 plug connector | |
Supply voltage | 2-wire HART (standard): - current consumption 4 ... 20 mA - min. terminal voltage 14 V (at 4 mA), 8 V (at 20 mA) - max. terminal voltage 36 V 4-wire HART: - DC version: voltage 10.5 ... 32 V, max. load 600 &Omega- - AC version: 90 ... 253 V, max. load 600 &Omega- PROFIBUS PA: 9 ... 32 V DC for additional information see technical information | |
Потребляемая мощность | 2-wire: 51 ... 800 mW 4-wire AC: max. 4 VA 4-wire DC, LUC-M10/LUC-M20: 330 ... 830 mW 4-wire DC, LUC-M30/LUC-M40: 0.6 ... 1 W | |
Current consumption | 2-wire devices: - HART: 3.6 ... 22 mA - PROFIBUS PA: max. 13 mA | |
Operating conditions | ||
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) , For further information see technical information. | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Физические/механические параметры | ||
Стандарты защищенности | with closed housing, tested according to - IP68, NEMA 6P (24 h at 1.83 m under water surface) - IP66, NEMA 4X with open housing: IP20, NEMA 1 (also ingress protection of the display) | |
Mechanical construction | ||
Dimensions | see section dimensions | |
Масса | LUC-M10: приблизительно 2.5 kg LUC-M20: приблизительно 2.6 kg LUC-M30: приблизительно 3.5 kg LUC-M40: приблизительно 3 kg | |
Материал корпуса | material in contact with process: - LUC-M10, LUC-M20: sensor PVDF, seal EPDM - LUC-M30: sensor UP and Нержавеющая сталь 1.4571/316Ti, seal EPDM, flange PP or Нержавеющая сталь 1.4571/316Ti - LUC-M40: sensor PVDF, seal Viton or EPDM, flange PP, PVDF or Нержавеющая сталь 1.4535/316L housing: - aluminium, seawater resistant, chromed, powder-coated cover: - aluminium, for version without on-site display - inspection glass for version with on-site display | |
Certificates and Сертификаты | ||
Ex approval | KEMA 05 ATEX 1111, KEMA 05 ATEX 1112 , for additional certificates see www.pepperl-fuchs.com | |
Type of protection | II 1/2G or II 2G EEx ia IIC T6 (KEMA 05 ATEX 1111) II 1/2G or II 2G EEx d [ia] IIC T6 (KEMA 05 ATEX 1111) II 1/2G or II 2G EEx em [ia] IIC T6 (KEMA 05 ATEX 1111) II 1/2D or II 2D or II 1/3D or II 3D T115°C or T100°C or T95°C (KEMA 05 ATEX 1111) II 1/2D or II 2D or II 1/3D or II 3D T115°C or T83°C or T84°C or T86°C (KEMA 05 ATEX 1112) II 3G EEx nA II T6 |
Совместимое оборудование | Наименование |