Ничего не куплено!
Поставки и внедрение датчиков, сенсоров, систем идентификации и контроля
Mail: prom@protonpc.ru
Тел: (495) 789-41-64 доб. 294
Application | ||
Function principle | The Pulscon LTC is a transmitter for continuous level measurement in powdery to granular bulk solids and liquids. The distance from the reference point (process connection of the measuring device) to the product surface is measured. High-frequency pulses are injected to a probe and led along the probe. The pulses are reflected by the product surface, received by the electronic evaluation unit and converted into level information. | |
Function and system design | ||
Measuring principle | The device is a measuring system that functions according to the time-of-flight method. The distance from the reference point (process connection of the measuring device) to the product surface is measured. | |
Equipment architecture | The Pulscon LTC is usable as single measuring cell or integrated in PROFIBUS PA systems. | |
Input characteristics | ||
Measured variable | distance between a reference point and a reflective surface (e. g. medium surface) | |
Measurement range | max. 35 m (115 ft), dependent on the medium, the probe type and the probe length - rod probe 6 mm: 0.3 ... 2 m (1 ... 6.6 ft) - rod probe 16 mm/coax probe: 0.3 ... 4 m (1 ... 13.2 ft) - rope probe: 1 ... 35 m (3 ... 115 ft) for details see technical information | |
Output characteristics | ||
Output signal | 4 ... 20 mA with HART Протокол PROFIBUS PA | |
Auxiliary energy | ||
Electrical connection | connection IH: 4 ... 20 mA with HART, 2-wire connection AH: 4 ... 20 mA with HART, 4-wire active, AC version connection DH: 4 ... 20 mA with HART, 4-wire active, DC versionconnection PA: PROFIBUS PA | |
Supply voltage | connection IH: 7.5 ... 36 V DC- Ex version: 7.5 ... 30 V DC connection AH: 90 ... 253 V AC connection DH: 10.5 ... 32 V DC | |
Потребляемая мощность | 60 ... 900 mW | |
Current consumption | connection AH: приблизительно 3 ... 6 mA connection DH: приблизительно 100 mA connection PA: max. 11 mA | |
Operating conditions | ||
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) , for details see technical information | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Физические/механические параметры | ||
Стандарты защищенности | with closed housing tested according to - IP68, NEMA 6P (24 h at 1.83 m (72 in) under water) - IP66, NEMA 4X with open housing: IP20, NEMA 1 (also degree of protection of display) Caution! Degree of protection IP68/NEMA 6P applies for M12 PROFIBUS PA plugs only when the PROFIBUS cable is plugged in. | |
Mechanical construction | ||
Dimensions | housing: - housing F12: 174 x 150 x 143 mm (6.8 x 6 x 5.6 in) - housing T12: 194 x 162 x 143 mm (7.6 x 6.4 x 5.6 in) distance sleeve: diameter 60 mm (2.36 in), height 400 mm (15.7 in) remote electronic: length 3000 mm (9.9 ft) process connections: length 61 ... 281.6 mm (2.4 ... 11.1 in) probes: - 4 mm (0.16 in) and 6 mm (0.24 in) rope probe: length 1000 ... 35000 mm (3 ... 115 ft) - 6 mm (0.24 in) rod probe: length 300 ... 2000 mm (1 ... 6.6 ft) - 16 mm (0.6 in) rod probe: length 300 ... 4000 mm (1 ... 13.2 ft) - coax probe: diameter 42.4 mm (1.67 in), length 300 ... 4000 mm (1 ... 13.2 ft) see section dimensions | |
Масса | housing F12 or T12: приблизительно 4000 g 4 mm (0.16 in) rope probe: приблизительно 100 g/m 6 mm (0.24 in) rod or rope probe: приблизительно 200 g/m 16 mm (0.63 in) rod probe: приблизительно 1600 g/m coax probe: приблизительно 3500 g/m process connections: depending on the design | |
Материал корпуса | housing: aluminium (AISi10Mg), seawater resistant, chromed, powder-coated transparent window: glass process connection: 1.4435/316L rope: 1.4401/316 rod and coax pipe: 1.4435/316L weight: 1.4435/316L | |
Certificates and Сертификаты | ||
Ex approval | KEMA 02 ATEX 1254 , for additional certificates see www.pepperl-fuchs.com | |
Type of protection | II 2G EEx em [ia] IIC T6 II 1/2G II EEx ia IIC T6 with WHG II 1/2G EEx d [ia] IIC T6 II 1/2G, II 1/3D EEx ia IIC T6 II 1/2G, II 1/3D EEx ia IIC T6 with WHG II 1/2G EEx ia IIC T6 II 1/3D transparent cover, dust-Ex II 1/2D aluminium cover, dust-Ex | |
SIL classification | до SIL2 acc. to IEC 61508, for 4 ... 20 mA output | |
Overspill protection | Z-65.16-368 (overspill protection in acc. with WHG) | |
Telecommunications | Complies with part 15 of the FCC rules for an unintentional radiator. All probes meet the requirements for a class A digital device (commercial, industrial or business environment). Coax probes and probes mounted in closed metallic vessels also meet the requirement for a class B digital device (residential environment). |
Совместимое оборудование | Наименование |
Level Control DTM | DTM collection |