Applications |
| Safety command devices: | Yes | |
| Electro-mechanical safety switches: | Yes | |
| Opto-electronic protective devices: | - | |
Functions |
| Safe device communication via EFI/SDL: | - | |
| Reset/restart: | Manual / automatic / configurable | |
Technical data |
| Fieldbus: | AS-Interface Safety at Work | |
| Safety integrity level: | SIL2 (IEC 61508) | |
| Category: | Safety slave, Category 3 (EN ISO 13849) | |
| Performance level: | PL d (EN ISO 13849) | |
| PFHd: | 1.07 * 1E-07 | |
| TM (mission time): | 10 a | |
| Maximum response time: | 4 ms | |
| Maximum power consumption: | 70 mA | |
| AS-Interface version: | 2.1 | |
| Data bits IN input channel I1: | AS-Interface Safety at Work code sequence on D0, D1 | |
| Data bits IN input channel I2: | AS-Interface Safety at Work code sequence on D2, D3 | |
| Data bits OUT LED alarm: | D0 | |
| Data bits OUT not used: | D1, D2, D3 (any) | |
| Maximum cable length socket I1/2: | 5 m | |
| Minimum opening time for the contacts socket I1/2: | 43 ms | |
| AS-interface voltage range: | 26.5 V DC ... 31.6 V DC | |
| Enclosure rating: | IP 65 (EN 60529) | |
| AS-Interface profile: | S-7.B.O. | |
| AS-Interface product group:: | AS-Interface Safety at Work | |
| Number of safety inputs: | 1 dual-channel | |
| System part: | Network solutions | |