Applications |
| Type of switching amplifier: | Contact expansion module | |
| Emergency stop pushbuttons: | - | |
| Safety switches: | - | |
| Safety Switch with mechanical lock: | - | |
| Two-hand control systems: | - | |
| Pressure sensitive mats: | - | |
| Opto-electronic protective devices: | - | |
| Opto-electronic protective devices without RES/EDM: | - | |
| Opto-electronic protective devices with RES/EDM: | - | |
| System part: | Safety relays | |
Functions |
| Cross-circuit detection: | - | |
| Reset/restart: | Automatic | |
| External device monitoring: | - | |
Technical data |
| Safety integrity level: | SIL3 (IEC 61508), SILCL3 (IEC 62061) 1) | |
| Category: | Category 4 (EN ISO 13849) 2) | |
| Performance level: | PL d (EN ISO 13849) 3) | |
| B10d parameter: | 1* 1E 06 switching cycles (AC-15, 230 V, I = 0.5 A) 3*1E 05 switching cycles (DC-13, 24 V, I = 2 A) 1.2 * 1E 06 switching cycles (DC-13, 24 V, I = 0.5 A) | |
| PFHd: | 2.0 * 1E-07 | |
| TM (mission time): | 4 a | |
| Width: | 22.5 mm | |
| Contact type: | Positively driven | |
| Number of enable current contacts: | 4 | |
| Number of delayed deactivation signalling current contacts: | 2 | |
| Delay time: | 1 s | |
| Operating voltage DC: | 24 V DC | |
| Maximum power consumption DC: | 2 W | |
| Type of output: | Relay contacts | |
| Rated operating current (voltage): | 6 A (230 V AC) 3600 switching cycles/h 6 A (24 V DC) 360 switching cycles/h 3 A (24 V DC) 3600 switching cycles/h | |
| Maximum switching current: | 6 A | |
| Maximum total current: | 12 A | |
| Mechanical life (relay contacts): | 1*1E 07 switching cycles | |
| Electrical life (relay contacts): | 2* 1E 06 switching cycles, dependent upon loading, details see operating instructions | |
| Enclosure rating: | IP 20 | |
| Ambient operating temperature from ... to: | -25 °C ... 55 °C | |
| Connection type: | Screw-type terminals | |
*изображение на сайте может отличаться от реального