Functions |
| Reset/restart: | Manual / automatic / configurable | |
| External device monitoring: | Yes | |
| Muting: | Yes | |
| Operating mode switching: | Yes | |
| Number of logical connections: | 255 | |
| Logical functions: | AND, NOT, OR, XNOR, XOR | |
| Application-specific logical functions: | Operating mode switch, Muting, Emergency stop, Presses, Two-hand control | |
| Safe device communication via EFI/SDL: | Yes | |
Electrical data |
| Supply voltage: | 24 V DC (16.8 V DC ... 30 V DC) | |
| Type of supply voltage: | PELV or SELV (the current of the power supply that powers the main unit must be limited to a maximum of 4 A, either through the power supply itself or a fuse.) | |
| Power consumption: | 2.5 W | |
| Short-circuit protection: | 4 A gG | |
| Number of EFI interfaces: | 2 | |
| Switch-on time of inputs: | 18 s | |
| Configuration interface: | Internal bus (FLEX BUS+) | |
Ambient data |
| Protection class standard: | EN/IEC 60529 | |
| Enclosure rating terminals: | IP 20 | |
| Vibration resistance: | 5 Hz ... 500 (EN 61131-2) | |
| Ambient operating temperature: | -25 °C ... 55 °C | |
| Storage temperature: | -25 °C ... 70 °C | |
| Air humidity: | 10 % ... 95 %, non-condensing | |
| Climate conditions according to: | EN 61131-2 (55 °C operating temperature, 95% rel. humidity) | |
| Electromagnetic compatibility (EMC): | EN 61000-6-2, EN 55011 EN 61131-2 (zone B) | |
| Connection type: | Plug | |
| Connection type EFI connection: | Cable gland | |
| Connection type EFI connection: | Plug-in spring terminals | |
| Dimensions (W x H x D): | 22.5 mm x 96.5 mm x 120.8 mm | |
| Weight: | 119 g | |
| Protection class according to IEC 60529:: | IP 40 | |
Safety-related parameters |
| Safety integrity level: | SIL3 (IEC 61508), SILCL3 (IEC 62061) | |
| Category: | Category 4 (EN ISO 13849) | |
| Performance level: | PL e (EN ISO 13849) | |
| PFHd: | 1.69 * 1E-09 | |
| TM (mission time): | 20 a | |